Cookie Img
Back to top
Home » Products » Air Handling Units » Single Skin Air Handling Unit

Single Skin Air Handling Unit

Single Skin Air Handling Unit
Single Skin Air Handling Unit
Product Code : 01
Price And Quantity
  • Minimum Order Quantity
  • 1
  • Unit of Measure
  • Piece/Pieces
Product Description

Primary Cooling Coil For Air Handling Unit


Abstract

It is great to introduce an energy-saving device into the air-handling unit (AHU). With an increase in the energy costs, an energy-saving device or system has become a preferred way in tropical states. In order to accomplish energy savings, the AHU is incorporated with a primary cooling coil system that helps recycle the condensate water. Also, there is effective recovery of latent heat of condensate water with the primary cooling coil that draws the warm outside fresh air. The measure of energy recovered is increased due to the large temperature gradient between condensate water and warm fresh air. This method is practical for primary AHU, which provides primary air to the air-conditioning system. The device offers long-term saving with negligible installation cost. And there is non-insulated drain pipe for drainage of de-cooled condensate water. The effective design of primary cooling coil helps accomplish the desirable cooling effect as well as energy saving.


Introduction

In tropical nations, such as Malaysia and United Arabia Emirates (UAE), the weather is hot & humid throughout the year. A lot of energy is used-up for Mechanical Ventilation (ACMV) and Air-Conditioning Systems. For instance, in hospitals and hotels, the energy is utilized to cool down the fresh air in the AHU and presented into the building for the required internal air quality. In the high humid environmental condition, a large amount of condensed water is drained away. However, it takes around 2% of the total cooling load for the cooled condensate water. The saving of the 2% of energy for a system can make a great reduction in the operating cost.

First, the condensed water is gathered by condensate drain pan, and then the collected water is pumped up into the cooling coil. Afterward, the de-cooling process is performed. For maximizing the energy recovery, install a primary cooling coil at AHU's fresh-air intake opening.

Technical Details :-


Model

CFM

Fan Model

Calarea (sqMtr.)

Height (mm)

Weight (mm)

Depth (mm)

DDSH-018

1100

180

0.20

750

900

1150

DDSH-028

1400

200

0.26

800

900

1200

DDSH-029

1800

225

0.33

800

1000

1300

DDSH-037

2200

250

0.41

900

1100

1350

DDSH-046

2800

280

0.51

1000

1100

1400

DDSH-059

3500

315

0.65

1000

1375

1450

DDSH-068

4000

355

0.74

1100

1375

1600

DDSH-074

4400

355

0.82

1100

1425

1600

DDSH-085

5000

400

0.94

1200

1425

1700

DDSH-093

5500

400

1.02

1200

1550

1700

DDSH-102

6000

450

1.12

1300

1550

1800

DDSH-115

6800

450

1.26

1300

1650

1800

DDSH-130

7700

500

1.43

1400

1900

2000

DDSH-144

8500

500

1.58

1400

1900

2000

DDSH-161

9500

560

1.77

1500

1900

2200

DDSH-183

10800

560

2.01

1500

2050

2200

DDSH-204

12000

630

2.23

1600

2050

2300

DDSH-229

13500

630

2.51

1600

2350

2300

DDSH-255

15000

710

2.79

1750

2350

2550

DDSH-289

17000

710

3.16

1750

2650

2550

DDSH-340

20000

800

3.78

2000

2650

2700

DDSH-365

21500

800

4.00

2000

2800

2700

DDSH-425

25000

900

4.65

2250

2800

2900

DDSH-459

27000

900

5.02

2250

3000

2900

DDSH-570

30000

1000

5.58

2500

3000

3000

DDSH-578

34000

1000

6.32

2500

3000

3000


Trade Information
  • Payment Terms
  • Cheque, Cash in Advance (CID), Cash Advance (CA)
  • Supply Ability
  • As per demand Per Week
  • Delivery Time
  • 1 Week
  • Packaging Details
  • Wooden Packing, As per product
  • Main Export Market(s)
  • Africa, Middle East, Western Europe, Eastern Europe, South America, North America, Central America, Australia, Asia
  • Main Domestic Market
  • All India
  • Certifications
  • ISO 9001:2015

DRYCOOL SYSTEMS INDIA (P) LTD.

Contact Us

( *represents compulsory fields )

Tips on getting accurate quotes. Please include product name, order quantity, usage, special requests if any in your inquiry.